Watts to Amps Calculator

Watts to Amps Calculator

Convert power in watts or kilowatts to current in amps — or amps back to watts. Choose DC, single-phase AC or three-phase AC, enter the voltage and, for AC, the power factor. You also see the current at other common voltages, from 12 V to 480 V.

Convert
Circuit
Power unit
For three-phase, the line-to-line voltage (208, 400 or 480 V, for example).
1 for heaters, kettles and incandescent lamps; about 0.8–0.9 for motors. It is on the motor nameplate.
Current (amps)12.5
Apparent power (VA)1,500
Power (kW)1.5

I = P ÷ (V × PF) = 1,500 W ÷ (120 V × 1) = 12.5 A

1,500 W at other common voltages
VoltageCurrent
100 V15 A
120 V12.5 A
220 V6.818 A
230 V6.522 A
240 V6.25 A

Calculated on your device · formulas checked against known results · How we test

How to convert watts to amps

  1. Choose the direction: watts to amps, or amps to watts.
  2. Choose the circuit: DC (batteries, solar panels, car and RV wiring), single-phase AC (household outlets) or three-phase AC (motors, workshops and commercial buildings).
  3. Enter the power or the current and the voltage. Use the nameplate or label of the appliance. For three-phase, enter the line-to-line voltage.
  4. Set the power factor for AC loads. It is 1 for purely resistive loads such as heaters, kettles and incandescent bulbs, and lower for motors, compressors and some power supplies.

You get the current, the apparent power in volt-amperes and the power in kilowatts, the formula with your numbers, and a table of the same load at other common voltages.

Watts to amps formulas

CircuitWatts to ampsAmps to watts
DCI = P ÷ VP = V × I
AC single-phaseI = P ÷ (V × PF)P = V × I × PF
AC three-phaseI = P ÷ (√3 × VL-L × PF)P = √3 × VL-L × I × PF

P is the real power in watts, V the voltage, I the current in amperes and PF the power factor (cos φ). √3 ≈ 1.732 appears in three-phase circuits because the line-to-line voltage is √3 times the voltage of each phase to neutral. If you only know the line-to-neutral voltage of a three-phase supply, use I = P ÷ (3 × VL-N × PF), which gives the same answer.

Worked examples

Common household voltages

The same appliance draws a different current depending on where you live. Nominal mains voltages:

RegionSingle-phaseThree-phase (line-to-line)
United States, Canada120 V (240 V for dryers, ranges, EV chargers)208 V or 480 V
Europe, UK, Australia, most of Asia and Africa230 V400 V
Saudi Arabia, Iraq, Egypt and much of the Arab world220–230 V (127 V in older Saudi buildings)380–400 V
Japan100 V (200 V for large appliances)200 V
Cars, trucks, RVs and solar systems12 V, 24 V or 48 V DC

Real power, apparent power and power factor

In AC circuits with motors or coils, current and voltage are out of step, so part of the current does no useful work. The real power (watts) is what turns into heat, light or motion and what your meter bills; the apparent power (volt-amperes, VA) is volts times amps and decides how large cables, fuses and generators must be. The ratio of the two is the power factor. A motor rated 10 kW at PF 0.85 takes as much current as a 11.8 kW heater.

The converter gives the running current. Motors draw several times that when they start, and wire sizing and breaker selection follow code tables (NEC Article 310 and 430 in the U.S., IEC 60364 in most other countries) — the voltage drop calculator checks whether a cable is long enough to matter. Have mains work done by a qualified electrician.

Frequently asked questions

How many amps is 1,500 watts?

At 120 V, 1,500 W is 12.5 A. At 230 V it is 6.5 A, and at 240 V it is 6.25 A — for a resistive load such as a heater with a power factor of 1.

How do I convert amps to watts?

Multiply amps by volts (and by the power factor for AC motors): P = V × I × PF. 10 A at 230 V with PF 1 is 2,300 W. For three-phase, multiply by √3 as well.

Can you convert watts to amps without the voltage?

No. Watts are volts times amps, so the same power means twice the current at half the voltage. A 60 W load draws 5 A at 12 V but only 0.5 A at 120 V.

How many amps does a 3-phase 10 kW load draw?

At 400 V and a power factor of 0.85 it draws about 17 A per line (10,000 ÷ (1.732 × 400 × 0.85)). At 480 V and PF 0.9 it is about 13.4 A.

What power factor should I use?

Use the value on the nameplate. Without it, 1 is right for heaters and incandescent lamps, about 0.85 is a reasonable estimate for induction motors at full load, and modern electronics with power factor correction are close to 0.95–1.

Embed this calculator on your website

Free for any website or blog. Paste this code where you want the calculator to appear:

All free calculator widgets

Last updated: October 19, 2026

Menu

Categories

Finance Calculators31 calculatorsBusiness & Shopping Calculators9 calculatorsHealth & Fitness Calculators16 calculatorsMath & School Calculators25 calculatorsDate & Time Calculators21 calculatorsHoliday Countdowns17 calculatorsEveryday Tools57 calculatorsMic, Camera & Sound Tools13 calculatorsDeveloper Tools11 calculatorsImage & PDF Tools23 calculatorsEngineering Calculators7 calculators

CalcWorthy

AboutContactPrivacy PolicyTerms of Use

Language

Language
EnglishEnglishالعربيةArabicবাংলাBanglaDeutschGermanEspañolSpanishفارسیPersianFrançaisFrenchעבריתHebrewहिन्दीHindiBahasa IndonesiaIndonesianItalianoItalian日本語Japanese한국어KoreanBahasa MelayuMalayNederlandsDutchPolskiPolishPortuguêsPortugueseРусскийRussianไทยThaiTürkçeTurkishУкраїнськаUkrainianاردوUrduTiếng ViệtVietnamese简体中文Simplified Chinese