Calculate duct area from airflow
The basic relationship for mean air velocity is Q = vA: volume flow equals mean velocity multiplied by cross-sectional area. In US HVAC units, cubic feet per minute divided by feet per minute gives square feet. Use the sizing mode when you already know the airflow and want the theoretical inside area at a target mean velocity. Use the checking mode when you know an actual duct diameter or width and height and want to see the corresponding mean velocity. These are geometry and continuity calculations, not a complete HVAC duct design.
Round and rectangular dimensions
A round duct has area pi times radius squared. When its diameter is entered in inches, divide the diameter by twelve to convert to feet before finding area. A rectangular duct has inside area equal to width times height, divided by 144 when both dimensions are in inches. The sizing mode finds the continuous round diameter that supplies the requested area, and a rectangular pair of dimensions using your chosen width-to-height ratio. The resulting sizes are theoretical; actual catalog ducts and fabricated dimensions may differ.
Worked example: 400 CFM at 700 feet per minute
Divide 400 CFM by 700 feet per minute to obtain approximately 0.5714 square foot of required inside area. A round opening with that area has an inside diameter of about 10.24 inches. For a rectangle twice as wide as it is tall, the theoretical width is about 12.83 inches and the height about 6.41 inches. If you instead have an actual 12 by 8 inch rectangular duct, its area is 96 square inches, or two-thirds of a square foot. At 400 CFM the average air velocity is 600 feet per minute.
What velocity does and does not tell you
Higher velocity through the same duct carries more volume, but it can also increase noise and pressure loss. The actual air delivered by a fan depends on its performance curve, filters, coils, dampers, fittings, branch balancing and total system resistance. A target velocity must be selected for the specific application; there is no universal safe number for all supply, return and exhaust systems. This calculator intentionally does not invent a friction-rate estimate from cross-section alone. Use manufacturer data and a recognized duct design method for a full pressure-loss calculation.
Field measurements and unit checks
Enter the clear inside dimensions, not nominal outside dimensions including insulation. If measuring airflow, use a suitable instrument and traverse method rather than assuming a single centerline reading equals the mean. The tool also converts the resulting velocity to meters per second and flow to cubic meters per hour, using exact foot and inch definitions. Results assume a steady average volumetric flow and do not correct for air density, leakage or compressibility. Confirm dimensions, local ventilation requirements and equipment limits before any construction or safety-critical use.
Frequently asked questions
Does the tool include pressure drop?
No. It calculates geometry and mean velocity, not friction or fittings.
Is the diameter a catalog size?
No. The sizing result is a theoretical inside diameter.
Can I use this for smoke extraction?
Not as a design approval. Smoke-control systems need specialist code and engineering checks.